Home > BRANDS > Fantech > Fantech Heat Recovery Ventilators & Energy Recovery Ventilators >

  Fantech KHP30000 Commercial Heat Recovery Ventilator 3790 CFM, 2 Speed



 
Our Price: $8,369.41
Request Large Quantity Quote


Free Ground Shipping for Orders over $2,000. Details



Product Code: FANTECH-KHP30000


Technical Spec Downloads
 
Technical Spec

Fantech KHP30000 Heat Recovery Ventilator
3790 CFM fan, Covers Up To 90,000 Square Feet Commercial.


Features and Benefits
  • Backward curved blade motors
  • Electrostatic filters (washable)
  • Aluminum heat recovery core
  • External screw type dry contacts
  • Improved core guide channels for easy removal of core
Specifications and Ratings
  • CASE 20 gauge galvanized steel for core housing. Blower case and filter case are pre-assembled & painted. Two (2) drain connections ¹⁄₂" NPT.
  • BLOWERS Two (2) belt driven blowers. Blowers come with galvanized wheel and housing. Blowers are rubber mounted to reduce noise and vibration.
  • MOTORS Two (2) totally enclosed, self-cooled, energy efficient motors with epoxy enamel finish. Featuring start capacitor, sleeve & ball bearing . KHP 20000 - 3/4 horsepower, single phase, 115/230 volts with over load protection, KHP 30000 - 1 horsepower, single phase, 115/230 volts with over load protection.
  • CORE Modular heat pipe core configured for efficient performance and retrieval of heat.
  • FILTERS Two (2) throw-away fiberglass filters in a drawer type filter rack. Filters are 1" thick. Cabinet for filters is insulated.
  • MOUNTING Unit can be installed using mounting brackets already fastened to the unit. Unit is mounted in place using threaded rods (purchased separately). The rods are then connected to the base plates provided with the bracket. The plates must be a minimum of 2" (50.8 mm) from the edge of the rail and in a range of 6" (152.4 mm) from each other. Unit can also be mounted by attaching it on a platform.
  • CONTROLS Low voltage (24VAC) external dry contacts to activate high speed. Two (2) speed controls for continuous ventilation speeds (one for each blower).
  • DEFROST The defrost sequence is activated when the exhaust air temperature drops below the preset level. The sensor shuts down the supply fan until the core defrosts and then the unit returns to normal operation.
  • SERVICEABILITY Cores, filters, blowers and drain pans can be accessed easily from two sides of the HRV through access panels.

Fantech KHP30000 Heat Recovery Ventilator diagram


Performance Data
Model KHP30000
Volts 230V
Rated Watts 1610
Max. Amps 7
CFM rated at 0.1" Static Pressure 3900
CFM rated at 0.2" Static Pressure 3800
CFM rated at 0.3" Static Pressure 3750
CFM rated at 0.4" Static Pressure 3650
CFM rated at 0.5" Static Pressure 3500

Share your knowledge of this product. Be the first to write a review »

Browse for more products in the same category as this item:

BRANDS > Fantech > Fantech Heat Recovery Ventilators & Energy Recovery Ventilators